8 comments

  • iamniels 22 minutes ago
    This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.

    I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.

    • api 18 minutes ago
      Also reduces energy use and nukes the water objection.
  • helsinkiandrew 30 minutes ago
    Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178

    I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan

    • IndrekR 18 minutes ago
      Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
      • andai 8 minutes ago
        So... good for Nvidia's profits?
  • __MatrixMan__ 36 minutes ago
    That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.
    • andai 7 minutes ago
      In Eastern Europe there's a lot of places that get hot water thru underground pipes from a power plant.

      Obviously has downsides though, one time they were renovating and we didn't have hot water for a few weeks.

    • yxhuvud 15 minutes ago
      Not for distribution, as it needs to be hot enough to kill legionalla.
    • deadbabe 17 minutes ago
      People do not want to bathe in your unethical cursed water that was used to cool chips creating AI content trained on stolen data!
  • yread 50 minutes ago
    Datacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling
    • mschuster91 21 minutes ago
      Evaporative cooling seems to be some American nonsense.

      Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].

      For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.

      [1] https://www.br.de/nachrichten/bayern/noch-haeufig-ungenutzte...

      [2] https://www.bayern-innovativ.de/emagazin/detail/tu-muenchen-...

      • maeln 2 minutes ago
        > Evaporative cooling seems to be some American nonsense.

        Don't quote me on that, but I remember OVH proudly advertising their new "passive" DC cooling system, which was based on evaporative cooling. The idea of using less energy, but more water was sold as "green" a few years back.

        A lot of the new DC getting out of the ground in China where also designed with evaporative cooling in mind. It's definitely not an "american nonsense". What is non sensed though is that both China and the U.S are building a lot of their DC designed with evaporative cooling in water stressed region right now. While it makes sense in terms of cooling (drier air makes evaporative cooling better), I don't think I have to mention the obvious problem of pumping tons of water in dry region.

      • entrope 6 minutes ago
        Some European data centers use evaporative cooling because they got permits long ago, they don't have the physical space for a non-evaporative system, or both. [1] and [2] (both Dutch, because I happened to go there for spring break this year and saw the coverage then) are two examples.

        [1]- https://www.techzine.nl/nieuws/infrastructure/577227/datacen... [2]- https://www.nrc.nl/nieuws/2026/08/16/nieuw-amerikaans-datace...

      • m4rtink 11 minutes ago
        It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
    • nekusar 22 minutes ago
      This is the dumbest comment line and perpetuates one facet of hate towards datacenter water consumption. Why?

      When water evaporates, where does it go?

      1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)

      2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

      Naturally, the heat is a problem. And running massive fossil fuels is stupid, given we could go all in on solar. But solar also reduces heat effects due to conversion to electricity. Add reflective cooling paint, and we'd be on our way of active cooling electricity generation.

      China's doing exactly this. USA? We just open up more closed oil wells, and double down on coal. Smells like, 1800s version of winning with a large dose of cancer.

      • maeln 6 minutes ago
        > When water evaporates, where does it go?

        > 1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)

        > 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

        Problem is, as far as I know, DC do not use rain / river / aquifer water straight up. Water needs to be processed, and processing water is not free. So you use a significant amount of energy to process water who will be just dumped to release heat.

        The other thing is, where the water is coming from and where it goes is very important. A lot of DC in China and the U.S right now are being built in drought prone regions. When you evaporate the water, there is no guarantee that it will rain in the same region. So you are draining the aquifer of already water-stressed region, to have it dumped as rain somewhere else that might not have water stress.

      • adrian_b 11 minutes ago
        Frequently, the water that goes into clouds from some place will not return through rain in the same place.

        If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.

        Only for datacenters built in rainy places it does not matter whether they evaporate water.

      • eminence32 13 minutes ago
        Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.

        Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.

      • mschuster91 18 minutes ago
        > 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain

        The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.

        But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.

        Friends don't let friends run evaporative cooling if there is literally any other way.

        • nekusar 12 minutes ago
          You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.

          Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.

          The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".

          And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".

  • ZiiS 3 minutes ago
    I know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.
  • ExoticPearTree 22 minutes ago
    ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).

    The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.

    Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.

    As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.

  • quickthrowman 23 minutes ago
    Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.

    1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling

    Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.

    https://mitchellt.com/2018/10/23/why-is-55-so-important.html

    The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)

  • cucumber3732842 55 minutes ago
    Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?

    There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.

    • samuelknight 30 minutes ago
      No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
    • lokar 47 minutes ago
      Sure, it expands to space of workable trade offs. Some times that will mean no chillers.